Home      About Us      Products      Resources      Feedback      Literature center      Training      Contact Us      FAQ

 
  

The following tables list attenuation and near-end crosstalk (NEXT) specifications from ANSI/TIA/EIA-568A for Category 3, Category 5 and 6 unshielded twisted pair (UTP) cables.

TABLE 1: HORIZONTAL UTP CABLE ATTENUATION dB/100M (dB/1000 FT)

FREQUENCY
(MHZ)
CATEGORY
3
CATEGORY
5e
CATEGORY
6
0.772 2.2 (6.7) 1.8 (5.5) 1.8 (5.5)
1.0 2.6 (7.9) 2.0 (6.1) 2.0 (6.1)
4.0 5.6 (17.1) 4.1 (12.5) 3.8 (11.6)
8.0 8.5 (25.9) 5.8 (17.7) 5.3 (16.2)
10.0 9.7 (29.6) 6.5 (19.8) 6.0 (18.3)
16.0 13.1 (39.9) 8.2 (25.0) 7.6 (23.2)
20.0 - 9.3 (28.4) 8.5 (25.9)
25.0 - 10.4 (31.7) 9.5 (29.0)
31.25 - 11.7 (35.7) 10.7 (32.6)
62.5 - 17.0 (51.8) 15.4 (47.0)
100.0 - 22.0 (67.1) 19.8 (60.4)
200.0 - - 29.0 (88.4)
250.0 - - 32.8 (100.0)

TABLE 2: HORIZONTAL UTP CABLE NEXT LOSS, dB (WORST PAIR COMBINATION) 100M (328 FT)

FREQUENCY
(MHZ)
CATEGORY
3
CATEGORY
5e
CATEGORY
6
0.772 43 67 76
1.0 41 65 274
4.0 32 56 65
8.0 27 52 61
10.0 26 50 59
16.0 23 47 56
20.0 - 45 55
25.0 - 44 53
31.25 - 42 52
62.5 - 38 47
100.0 - 35 44
200.0 - - 40
250.0 - - 38